Bichlbäck

Food and beverage

Sub-Sector: Bread, Biscuites, Cakes
Project Name:  Bichlbaeck fact_sheet_icon_25
(click to open fact sheet and detailed project description)

 

Changes in the production and energy supply:

  • Heat Integration
  • Storage
  • Energy efficiency

Project Description:
The company decided to invest in a heat exchanger to utilize waste heat of the shock freezer. In total 7,366 kWh/year of waste heat a 38 °C are available. The heat is stored in an existing 500 l hot water storage which is currently loaded with a gas burner. The storage supplies several processes with 60 °C hot water. In total the heat demand is 6,536 kWh/year. Due to temperature limitations only 3,660 kWh/year of waste heat can actually be used.

External link to further information: www.bichlbaeck.at

Go back to the Best Practice Examples Overview.